Qipudata
San Francisco · v0.7.1
qipu data›San Francisco›Places›University Mound pressure zone

University Mound pressure zone

Named in the records1985–2035

14 records of San Francisco tie this place, 1985–2035: 0 decisions of the Board of Supervisors and 14 facts read from city reports. Open the full list, with filters for years, kind and outcome.

Kind
Named in the records
Records
14: 0 Board decisions, 14 facts from city reports
Years
1985–2035

What the records say

All 14 records, in date order. The one-line summaries were written by a language model from the printed page; open the page to check the wording.

WhenWhat the record saysOutcomeSource
1985University Mound pressure zone water mains · finding: Mains serving Downtown cross areas of random fill where numerous breaks are likely (Cornell, O'Rourke 1985)findingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone - Use of existing Francisco Reservoir · alternative: Re-connection of existing 135-foot Francisco Reservoir offers minimal pressure benefitalternativeCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone - PRVs from Sunset or Lombard zone · alternative: Install pressure reducing valves at connections to the Marina District from Sunset pressure zone or Lombard ReservoiralternativeCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pipelines · other: two 48-inch pipes from reservoir reduced to 24-inch at far northern end of zonebuildingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone · other: service area extends from the bay shore up to about elevation 90 feetsiteCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone · finding: areas below elevation 13 feet adequate for 40 psi pressures at hydraulic gradeline below 105 feetfindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone · finding: Hydraulic grade line about 133.0 feet at Larkin & Bay Streets under maximum day demandfindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone · finding: some pressures below the desired 40 psifindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone required fire fighting storage · other: Primary 12,000 gpm; secondary 6,000 gpm; 12-hour volume 12.96 MG; 0.4 days of average day demandfindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone · other: about 1.5 million gallons of storage required for each hour of emergency supplyfindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
1990University Mound pressure zone · other: emergency storage reserve 3.3 daysfindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
2035University Mound pressure zone · other: 36.5 mgd requiredfindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
2035University Mound pressure zone · other: year 2035 average day demandmeasureCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗
2035University Mound pressure zone · other: ultimate average day demand 38.7 mgd (27,000 gpm) adequatefindingCity report: Final report Balboa and Francisco Reservoirs needs assessment
scanned page ↗

All 14 records, with filters · this place's data as JSON · release v0.7.1 · CC0 1.0