Qipudata
San Francisco · v0.9.2

Records › City reports › Final report Balboa and Francisco Reservoirs needs assessment (1990)

Cover of the report
City report · study · 1990

Final report Balboa and Francisco Reservoirs needs assessment (1990)

Final report Balboa and Francisco Reservoirs needs assessment

A study by the City's Public Utilities Commission assessing the need for and upgrades to the Balboa and Francisco Reservoirs and the water supply they serve. Scan on the Internet Archive ↗

Cost
about $4.3 million (1990 dollars)Scan 140 ↗
Storage
5.8 million gallons raised FranciscoScan 228 ↗
Balboa capacity
150 million gallons at 312 feetScan 34 ↗
Reserve storage
3.3 days of reserve storageScan 228 ↗
Findings
  • The report concludes the Crosstown pipe line cannot handle maximum day demands.Scan 208 ↗
Report recommendations
  • The report proposes raising Francisco Reservoir to 145 feet, which would provide about 5.8 million gallons of storage.Scan 228 ↗
  • It may be necessary to repair small cracks in the lining or reline the entire reservoir to fill and use the basins.Scan 34 ↗
22 quotes from the scan

Printed words Quoted from the page as read from the scan.

FindingPrinted words, misread in placess-05bfce001cf3

“The two asphalt-concrete lined basins have never been used for water stora, c.”

Scan 34

Backgrounds-1751b687cd7b

“The City of San Francisco is subdivided into eleven principal pressure zones, each fed by gravity from reservoirs with capacities ranging from 1.1 to 176.7 million gallons.”

Scan 34

Findings-26cbfadd0ba3

“The north basin is presently used as a parking lot for the College.”

Scan 34

Report recommendations-9a015af274fa

“When filled, the total capacity of the two reservoir basins would be 150 million gallons at an overflow elevation of 312 feet.”

Scan 34

Report recommendations-b9834619e457

“In order to fill and use the basins it may be necessary to repair small cracks in the lining or reline the entire reservoir.”

Scan 34

Findings-f7cca7889300

“Table 2-1 shows over 412 million gallons (MG) of gravity-flow, potable water storage within the City.”

Scan 34

Findings-8d75a0549737

“For this study, a 150 percent ratio of maximum day to average day demand was agreed upon by City staff and is used for all pressure zones.”

Scan 100

Findings-9906af587a6a

“East Bay Municipal Utility District (EBMUD) uses a maximum day factor of 170 percent of average day for areas west of the Berkeley/Oakland hills.”

Scan 100

Findings-b64ea0391494

“A 225 percent ratio of peak hour demand to average day demand was agreed upon and is used for all pressure zones.”

Scan 100

Findings-bf4a75c149f8

“Balboa Reservoir is located adjacent to the Crosstown pipeline connecting Sunset and College Hil] Reservoirs, and is at an elevation intermediate to these reservoirs.”

Scan 100

Findings-e7a6754b9d19

“Taken together, University Mound, Sunset, and College Hill pressure zones account for 80 percent of total City water demand.”

Scan 100

Findings-0a2635637bf3

“The ESA study predicts a permanent seismically-induced deformation on the order of 1 to 2 inches in the embankment slopes during the maximum credible earthquake.”

Scan 120

Findings-6c0e906ce4b3

“The ESA study indicates that a dense zone of foundation soils (with SPT blow counts ranging from 32 to 50) in the southeast corner of the southern embankment has liquefaction potential during the maximum credible earthquake.”

Scan 120

Report recommendations-6e2a961a132d

“The estimated cost to upgrade the Francisco Reservoir will be about $4.3 million dollars.”

Scan 140

Report recommendations-1b004567bb31

“Balboa Reservoir could provide a direct, gravity-fed supply in the event of a failure of the College Hill supply system.”

Scan 208

Report recommendations-4a89aff77dd3

“Integration of Francisco Reservoir into the University Mound System would reduce the demand on University Mound by 2.2 mgd.”

Scan 208

Report recommendations-76f6804c0c23

“Enlargement of the connection between the Sunset and Francisco zones would provide a secondary supply route to University Mound, without use of the Crosstown pipeline.”

Scan 208

Report recommendations-9466d051bde8

“Under ultimate demand conditions, the average day capacity that would be required from this line would be 53.0 mgd.”

Scan 208

Findings-e8856b7647d9

“Thus the pipeline does not have the capacity to handle maximum day demands.”

Scan 208

Report recommendations-177d2353d7af

“Raising Francisco Reservoir to an overflow elevation of 145 feet would provide about 5.8 million gallons of storage, using the footprint of the existing reservoir.”

Scan 228

Report recommendations-43f4d2acf081

“This would provide an additional 2.1 days of storage for the Marina District.”

Scan 228

Report recommendations-c96a55b5b257

“To derive pressure benefits, and to achieve compatibility with the present water system hydraulics, the existing reservoir would be raised to about 145 feet.”

Scan 228